Midea AC P6 error code

What it means

Condenser high temperature protection

Usual causes

  • Condenser temperature above 65°C (stops
  • restarts below 52°C)
  • High outdoor temperature
  • Dirty condenser
  • Blocked pipe
  • Condenser sensor wrong
  • Outdoor main board

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If P6 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Measure condenser temperature
  • Check T3 sensor resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).