Midea AC error codes – Multi-split outdoor M2/M3/M4 OC - outdoor digital tube
Midea AC P3 error code
What it means
Compressor current protection
Usual causes
- Input current too high (limits: 8.5 A small units, 15 A for 18-21K and 27K 1x3, 18.5 A 27K 1x4, 21.5 A 36K)
- High outdoor temperature
- Poor ventilation
- Dirty condenser
- Blocked pipe
- Outdoor main board
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If P3 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Clamp the supply current
- Check refrigerant system, site temperature, airflow, condenser
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).