Midea AC error codes – Multi-split outdoor M2/M3/M4 OC - outdoor digital tube
Midea AC P0 error code
What it means
Compressor discharge or top temperature protection (M4OC-27/36: discharge only)
Usual causes
- Gas shortage / leak
- Discharge sensor wiring wrong
- Discharge sensor faulty
- Outdoor main board fault
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If P0 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Is discharge temperature really above 115°C?
- Check sensor wiring to PCB
- Check for leaks
- Measure discharge sensor. Discharge sensor T5 (Appendix 2): 54.9 kΩ at 25°C, 29.2k at 40°C, 19.7k at 50°C, 5 kΩ at 90°C
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).