Midea AC P1 error code

What it means

High pressure protection (M4OC1-27, M4OC-27, M4OC-36)

Usual causes

  • HP switch wiring loose
  • HP switch broken
  • Very high outdoor temperature
  • Poor ventilation around outdoor unit
  • Dirty condenser
  • Blocked refrigerant pipe
  • Outdoor main board

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If P1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Check HP switch wiring
  • Short the HP switch socket temporarily - if unit runs, switch is bad
  • Check site temperature, airflow, condenser

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).