Midea AC error codes – Multi-split outdoor M2/M3/M4 OC - outdoor digital tube

15 codes from the Midea service manual, with what each one means and the usual causes. Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

E0

Outdoor EEPROM malfunction

Usual causes

  • EEPROM chip loose (socket type)
  • Outdoor main board fault
Book a technician for E0

E1

Room A indoor coil outlet sensor (T2B) or its connector defective

Usual causes

  • Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
  • Sensor open/short
  • Outdoor PCB
What our technician checks
  • Check T2B sensor of that room and connector on outdoor PCB
  • Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for E1

E2

Room B indoor coil outlet sensor (T2B) or its connector defective

Usual causes

  • Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
  • Sensor open/short
  • Outdoor PCB
What our technician checks
  • Check T2B sensor of that room and connector on outdoor PCB
  • Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for E2

E3

Room C indoor coil outlet sensor (T2B) or its connector defective

Usual causes

  • Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
  • Sensor open/short
  • Outdoor PCB
What our technician checks
  • Check T2B sensor of that room and connector on outdoor PCB
  • Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for E3

E6

Room D indoor coil outlet sensor (T2B) or its connector defective

Usual causes

  • Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
  • Sensor open/short
  • Outdoor PCB
What our technician checks
  • Check T2B sensor of that room and connector on outdoor PCB
  • Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for E6

E4

Outdoor temperature sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for E4

E5

Compressor voltage protection

Usual causes

  • Supply voltage wrong (should be about 220 V AC, unit works 190-264 V)
  • Power board fault
  • Bridge rectifier fault
  • IPM board fault
What our technician checks
  • Measure outdoor L-N: about 220 V AC
  • Measure IPM board P-N: 280-400 V DC
  • Rectifier: input 220-230 V AC gives about 310 V DC
Book a technician for E5

E7

Communication fault between IPM board and outdoor main board

Usual causes

  • IPM-to-main-board cable loose
  • IPM board fault
  • Outdoor main PCB fault
What our technician checks
  • Check IPM board for its own error display
  • Re-seat connecting cable
Book a technician for E7

P0

Compressor discharge or top temperature protection (M4OC-27/36: discharge only)

Usual causes

  • Gas shortage / leak
  • Discharge sensor wiring wrong
  • Discharge sensor faulty
  • Outdoor main board fault
What our technician checks
  • Is discharge temperature really above 115°C?
  • Check sensor wiring to PCB
  • Check for leaks
  • Measure discharge sensor. Discharge sensor T5 (Appendix 2): 54.9 kΩ at 25°C, 29.2k at 40°C, 19.7k at 50°C, 5 kΩ at 90°C
Book a technician for P0

P1

High pressure protection (M4OC1-27, M4OC-27, M4OC-36)

Usual causes

  • HP switch wiring loose
  • HP switch broken
  • Very high outdoor temperature
  • Poor ventilation around outdoor unit
  • Dirty condenser
  • Blocked refrigerant pipe
  • Outdoor main board
What our technician checks
  • Check HP switch wiring
  • Short the HP switch socket temporarily - if unit runs, switch is bad
  • Check site temperature, airflow, condenser
Book a technician for P1

P2

Low pressure protection (M4OC1-27, M4OC-27, M4OC-36)

Usual causes

  • LP switch wiring loose
  • LP switch broken
  • Outdoor temperature too low
  • Refrigerant leak (pressure below 0.14 MPa)
  • Blocked pipe
  • Outdoor main board
What our technician checks
  • Check LP switch wiring
  • Short the LP switch socket temporarily - if unit runs, switch is bad
  • Gauge on service port: below 0.14 MPa = leak
Book a technician for P2

P3

Compressor current protection

Usual causes

  • Input current too high (limits: 8.5 A small units, 15 A for 18-21K and 27K 1x3, 18.5 A 27K 1x4, 21.5 A 36K)
  • High outdoor temperature
  • Poor ventilation
  • Dirty condenser
  • Blocked pipe
  • Outdoor main board
What our technician checks
  • Clamp the supply current
  • Check refrigerant system, site temperature, airflow, condenser
Book a technician for P3

P4

IPM module protection

Usual causes

  • IPM P-N voltage wrong (needs 277-356 V DC for 14-27K, 277-410 V DC for 36K)
  • Supply not 220-240 V
  • Loose cable main board-IPM
  • Compressor leads loose / wrong
  • Bridge rectifier shorted
  • Reactor wire broken (∞ Ω) or PFC module faulty (M5OA-36)
  • IPM module, main board or compressor faulty
What our technician checks
  • Measure P-N on IPM
  • Check supply voltage and wiring
  • Check cable main board-IPM and compressor connections
  • Measure bridge rectifier: no terminal pair should read 0 Ω
  • Measure reactor: open (∞) = broken
  • Compressor phase-phase U-V, U-W, V-W 60-150 V AC when running
Book a technician for P4

P6

Condenser high temperature protection

Usual causes

  • Condenser temperature above 65°C (stops
  • restarts below 52°C)
  • High outdoor temperature
  • Dirty condenser
  • Blocked pipe
  • Condenser sensor wrong
  • Outdoor main board
What our technician checks
  • Measure condenser temperature
  • Check T3 sensor resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for P6

P7

Inverter compressor drive protection

Usual causes

  • Same as IPM protection: supply, P-N voltage, IPM, compressor, reactor
What our technician checks
  • Follow IPM module protection checks
Book a technician for P7

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.