Midea AC error codes – Multi-split outdoor M2/M3/M4 OC - outdoor digital tube
Midea AC P4 error code
What it means
IPM module protection
Usual causes
- IPM P-N voltage wrong (needs 277-356 V DC for 14-27K, 277-410 V DC for 36K)
- Supply not 220-240 V
- Loose cable main board-IPM
- Compressor leads loose / wrong
- Bridge rectifier shorted
- Reactor wire broken (∞ Ω) or PFC module faulty (M5OA-36)
- IPM module, main board or compressor faulty
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If P4 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Measure P-N on IPM
- Check supply voltage and wiring
- Check cable main board-IPM and compressor connections
- Measure bridge rectifier: no terminal pair should read 0 Ω
- Measure reactor: open (∞) = broken
- Compressor phase-phase U-V, U-W, V-W 60-150 V AC when running
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).