Maheshwari HVAC Solutions

Midea AC P6 error code

What it means

IPM module protection

Usual causes

  • IPM P-N voltage wrong (needs 277-356 V DC for 14-27K, 277-410 V DC for 36K)
  • Supply not 220-240 V
  • Loose cable main board-IPM
  • Compressor leads loose / wrong
  • Bridge rectifier shorted
  • Reactor wire broken (∞ Ω) or PFC module faulty (M5OA-36)
  • IPM module, main board or compressor faulty

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If P6 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Measure P-N on IPM
  • Check supply voltage and wiring
  • Check cable main board-IPM and compressor connections
  • Measure bridge rectifier: no terminal pair should read 0 Ω
  • Measure reactor: open (∞) = broken
  • Compressor phase-phase U-V, U-W, V-W 60-150 V AC when running

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: This model uses its own outdoor code list.