Midea AC error codes – Multi-split indoor - NEOLA, PREMIER, OASIS series
Midea AC P1 error code
What it means
Over / under voltage protection
Usual causes
- Supply voltage wrong (should be about 220 V AC, unit works 190-264 V)
- Power board fault
- Bridge rectifier fault
- IPM board fault
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If P1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Measure outdoor L-N: about 220 V AC
- Measure IPM board P-N: 280-400 V DC
- Rectifier: input 220-230 V AC gives about 310 V DC
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Operation lamp flashes N times; Timer lamp off for E codes, on for F codes, flashing for P codes.