Maheshwari HVAC Solutions

Midea AC E6 error code

What it means

Room D indoor coil outlet sensor (T2B) or its connector defective

Usual causes

  • Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
  • Sensor open/short
  • Outdoor PCB

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If E6 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Check T2B sensor of that room and connector on outdoor PCB
  • Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: Outdoor LED shows "--" standby, running frequency when running, "dF" in defrost. Press SW1 to step through check data (1 demand, 2 mode, 4 fan, 5-8 coil outlet temps, 9 condenser, 10 ambient, 11 discharge, 12 inverter current).