Midea AC error codes – Multi-split outdoor M5OA-36HRDN1-Q
Midea AC F5 error code
What it means
Room E coil outlet sensor defective
Usual causes
- Coil outlet (T2B) sensor of that indoor room or its connector on the OUTDOOR board loose
- Sensor open/short
- Outdoor PCB
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If F5 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Check T2B sensor of that room and connector on outdoor PCB
- Measure resistance. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: This model uses its own outdoor code list.