Midea AC F1 error code

What it means

T4 outdoor ambient sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If F1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: Operation lamp flashes N times; Timer lamp off for E codes, on for F codes, flashing for P codes.