Midea AC error codes – Multi-split indoor - NEOLA, PREMIER, OASIS series
Midea AC F3 error code
What it means
T5 discharge sensor open/short
Usual causes
- Sensor connector loose
- Sensor open or short
- PCB input circuit fault
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If F3 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Check connection
- Measure T5. Discharge sensor T5 (Appendix 2): 54.9 kΩ at 25°C, 29.2k at 40°C, 19.7k at 50°C, 5 kΩ at 90°C
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Operation lamp flashes N times; Timer lamp off for E codes, on for F codes, flashing for P codes.