Carrier AC xL0 error code

What it means

DC compressor (inverter) module error

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If xL0 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Compressor U-V-W 0.9-5 Ω each pair and equal, infinite to ground. Module: P-N = 1.41 × supply
  • terminals 1-2 = 510-580 V DC. With 3,4,5 disconnected, all terminal pairs infinite (≈0 = module damaged). DC bus wire direction through inductor must follow arrow.

From the Carrier service manual. These checks use meters and live power – for trained technicians only.

About this series: Codes with x prefix: x = system (1 = A, 2 = B). P-codes that repeat lock out as H4/H5/H6/H9 and need power reset.