Carrier AC error codes – VRF Full DC Inverter - outdoor unit
Carrier AC xL0 error code
What it means
DC compressor (inverter) module error
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If xL0 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Compressor U-V-W 0.9-5 Ω each pair and equal, infinite to ground. Module: P-N = 1.41 × supply
- terminals 1-2 = 510-580 V DC. With 3,4,5 disconnected, all terminal pairs infinite (≈0 = module damaged). DC bus wire direction through inductor must follow arrow.
From the Carrier service manual. These checks use meters and live power – for trained technicians only.
About this series: Codes with x prefix: x = system (1 = A, 2 = B). P-codes that repeat lock out as H4/H5/H6/H9 and need power reset.