Carrier AC xL2 error code

What it means

DC bus high voltage protection

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If xL2 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • DC 1-2 above 580 V: measure across the two electrolytic capacitors (510-580 V, meter on 1 kV range)
  • check supply too high / unstable.

From the Carrier service manual. These checks use meters and live power – for trained technicians only.

About this series: Codes with x prefix: x = system (1 = A, 2 = B). P-codes that repeat lock out as H4/H5/H6/H9 and need power reset.