35 codes from the Carrier service manual, with what each one means and the usual causes. Codes with x prefix: x = system (1 = A, 2 = B). P-codes that repeat lock out as H4/H5/H6/H9 and need power reset.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

E0

Communication error between outdoor units (shown on slave)

What our technician checks
  • Master address 0, slaves below 4. H1-H1, H2-H2 wiring between ODUs, shielded, no open/short. Check PCB chips seated, pins, moisture.
Book a technician for E0

E1

Phase sequence reversed or phase loss

What our technician checks
  • Phase sequence (auto-check only at first power-on). Loose power wire at terminals, lost phase.
Book a technician for E1

E2

Communication error with indoor units (shown on master)

What our technician checks
  • Check P-Q-E communication wire for open/short (measure resistance), daisy-chain (hand-in-hand) layout, shielding, distance from power cables, lamps/transformers nearby, wire length. All IDUs powered? Duplicate addresses? Voltage P/Q to E about DC 2.5 V (0 V or 5 V = 485 chip faulty).
Book a technician for E2

E4

Outdoor ambient sensor (T4) error

What our technician checks
  • Sensor connection to PCB
  • sensor open/short.
Book a technician for E4

E5

Voltage protection

What our technician checks
  • Measure supply voltage, all phases, under load.
Book a technician for E5

E8

Outdoor unit address error

What our technician checks
  • ENC1 address must be 0-3. Check dial switch, 74HC165N chip, PCB connection wire.
Book a technician for E8

xE9

S11 setting does not match capacity

What our technician checks
  • S11 and ENC2 (capacity switch) must match the outdoor unit capacity.
Book a technician for xE9

xH0

Communication error between DSP (IR341) and main chip

What our technician checks
  • Power supply / phase loss
  • transformer on main board
  • interference
  • chip seating.
Book a technician for xH0

H1

Communication error between 0537 chip and main chip

What our technician checks
  • 0537 chip, main chip, interference, pins, moisture.
Book a technician for H1

H2also H3

Number of outdoor units decreased (main unit)

What our technician checks
  • Signal wire between ODUs loose
  • ODU addresses
  • any ODU powered off
  • all ODUs on unified power.
Book a technician for H2

H3

Number of outdoor units increased (main unit)

What our technician checks
  • Same as H2: signal wire, addresses, unified power.
Book a technician for H3

H4

P6 inverter-module protection 3 times in 60 min

What our technician checks
  • See P6 / L-codes. Press query button to read the L-code.
Book a technician for H4

H5

P2 low-pressure protection 3 times in 60 min

What our technician checks
  • See P2.
Book a technician for H5

H6

P4 discharge-temp protection 3 times in 100 min

What our technician checks
  • See P4.
Book a technician for H6

H7

Number of indoor units decreased (IDU lost > 3 min)

What our technician checks
  • Check P-Q-E communication wire for open/short (measure resistance), daisy-chain (hand-in-hand) layout, shielding, distance from power cables, lamps/transformers nearby, wire length. All IDUs powered? Duplicate addresses? Voltage P/Q to E about DC 2.5 V (0 V or 5 V = 485 chip faulty). IDU control board / 485 IC.
Book a technician for H7

H8

High-pressure sensor error (Pc ≤ 0.3 MPa)

What our technician checks
  • Sensor connector and supply
  • compare with gauge.
Book a technician for H8

H9

P9 DC fan protection 3 times in 60 min

What our technician checks
  • See P9.
Book a technician for H9

Hb

Low-pressure sensor open/short

What our technician checks
  • Sensor connector, open/short.
Book a technician for Hb

xHd

Auxiliary (slave) outdoor unit error

What our technician checks
  • x = which auxiliary unit (1Hd = aux unit 1). Read the code on that unit.
Book a technician for xHd

P0

Inverter compressor top temperature protection

What our technician checks
  • Low charge / leak
  • outdoor fan
  • coil dirty
  • ODUs too close (air short-circuit)
  • too many IDUs
  • air/N2 in system
  • blockage on low side (frost).
Book a technician for P0

P1

High-pressure protection

What our technician checks
  • ODUs too close, fan broken, dirty coil, liquid pipe blocked, valve not opened, air/N2 in system, overcharge.
Book a technician for P1

P2

Low-pressure protection (3× in 60 min → H5)

What our technician checks
  • Lack of refrigerant/leak, gas pipe blocked, gas valve closed, EXV blocked, indoor fan not running, dirty indoor coil/filter.
Book a technician for P2

xP3

Compressor current protection

What our technician checks
  • Excess load, overcharge, poor outdoor heat exchange, air/N2, power wiring short. Compressor terminals 1-5 Ω between any two, infinite to earth.
Book a technician for xP3

P4

Discharge temperature protection (3× in 100 min → H6)

What our technician checks
  • Same as P0: low charge, airflow, air in system, blockage.
Book a technician for P4

P5

High condenser temperature protection

What our technician checks
  • T3 sensor connection
  • excess load
  • poor outdoor heat exchange
  • air/N2
  • liquid-side blockage
  • outdoor fan motor.
Book a technician for P5

xP6

Inverter module protection (3× in 60 min → H4)

What our technician checks
  • Press query button within 1 min to read the L-code (L0-L9) and follow it.
Book a technician for xP6

P9

DC fan module protection (3× in 60 min → H9)

What our technician checks
  • Control box / ambient too hot, fan module heatsink, wires between fan module and main PCB, P-N voltage on module, fan motor blocked. Swap module into another ODU to test.
Book a technician for P9

xL0

DC compressor (inverter) module error

What our technician checks
  • Compressor U-V-W 0.9-5 Ω each pair and equal, infinite to ground. Module: P-N = 1.41 × supply
  • terminals 1-2 = 510-580 V DC. With 3,4,5 disconnected, all terminal pairs infinite (≈0 = module damaged). DC bus wire direction through inductor must follow arrow.
Book a technician for xL0

xL1

DC bus low voltage protection

What our technician checks
  • DC 1-2 terminals 510-580 V. Below 510 V: check rectifier wiring for looseness.
Book a technician for xL1

xL2

DC bus high voltage protection

What our technician checks
  • DC 1-2 above 580 V: measure across the two electrolytic capacitors (510-580 V, meter on 1 kV range)
  • check supply too high / unstable.
Book a technician for xL2

xL4

MCE error / synchronisation / closed loop

What our technician checks
  • Same as L1: DC bus 510-580 V, rectifier wiring, module and circuit.
Book a technician for xL4

xL5

Zero speed protection

What our technician checks
  • Electric circuit and compressor.
Book a technician for xL5

xL7

Phase sequence error (compressor)

What our technician checks
  • Module and U/V/W wiring order.
Book a technician for xL7

xL8

Speed change > 15 Hz within one second

What our technician checks
  • Compressor U-V-W 0.9-5 Ω, infinite to ground. Swap test: run compressor from a healthy system's control box (U,V,W in order).
Book a technician for xL8

xL9

Set vs actual speed differs > 15 Hz

What our technician checks
  • Same as L8.
Book a technician for xL9