Carrier AC xP3 error code

What it means

Compressor current protection

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If xP3 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Excess load, overcharge, poor outdoor heat exchange, air/N2, power wiring short. Compressor terminals 1-5 Ω between any two, infinite to earth.

From the Carrier service manual. These checks use meters and live power – for trained technicians only.

About this series: Codes with x prefix: x = system (1 = A, 2 = B). P-codes that repeat lock out as H4/H5/H6/H9 and need power reset.