Maheshwari HVAC Solutions

Carrier AC E1 error code

What it means

Indoor-outdoor communication error

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If E1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Check P-Q-E communication wire for open/short (measure resistance), daisy-chain (hand-in-hand) layout, shielding, distance from power cables, lamps/transformers nearby, wire length. All IDUs powered? Duplicate addresses? Voltage P/Q to E about DC 2.5 V (0 V or 5 V = 485 chip faulty). 485 chip 13089 on IDU board.

From the Carrier service manual. These checks use meters and live power – for trained technicians only.

About this series: Hi-wall and cassette use some codes differently (E0) - check the indoor type.