Carrier AC error codes – VRF Full DC Inverter - indoor units
Carrier AC E1 error code
What it means
Indoor-outdoor communication error
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If E1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Check P-Q-E communication wire for open/short (measure resistance), daisy-chain (hand-in-hand) layout, shielding, distance from power cables, lamps/transformers nearby, wire length. All IDUs powered? Duplicate addresses? Voltage P/Q to E about DC 2.5 V (0 V or 5 V = 485 chip faulty). 485 chip 13089 on IDU board.
From the Carrier service manual. These checks use meters and live power – for trained technicians only.
About this series: Hi-wall and cassette use some codes differently (E0) - check the indoor type.