Midea AC error codes – Multi-split indoor - 9V, Vertu, 9A, Corona, R, Y, X series
Midea AC E1 error code
What it means
Indoor / outdoor communication error
Usual causes
- Wrong / loose wiring between indoor and outdoor terminals
- Signal line S fault
- IPM or PFC board not powered (multi outdoor)
- Reactor disconnected
- Wrong number of indoor units detected
- Indoor or outdoor PCB fault
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If E1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Power off at breaker, power on again
- Check wiring follows the wiring diagram
- Measure Vs (voltage between S and L2/N): it should swing between positive and negative
- With all indoors off, check IPM power LED on and PFC LED (qua-zone)
- Outdoor check button: press 18 times to see how many indoor units are detected (2 dual, 3 tri, 4 quad)
From the Midea service manual. These checks use meters and live power – for trained technicians only.
About this series: Indoor display code. Glory series shows the same faults by DEF/TIMER/AUTO/RUN lamps (see led).