Midea AC E1 error code

What it means

Indoor / outdoor communication error

Usual causes

  • Wrong / loose wiring between indoor and outdoor terminals
  • Signal line S fault
  • IPM or PFC board not powered (multi outdoor)
  • Reactor disconnected
  • Wrong number of indoor units detected
  • Indoor or outdoor PCB fault

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If E1 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Power off at breaker, power on again
  • Check wiring follows the wiring diagram
  • Measure Vs (voltage between S and L2/N): it should swing between positive and negative
  • With all indoors off, check IPM power LED on and PFC LED (qua-zone)
  • Outdoor check button: press 18 times to see how many indoor units are detected (2 dual, 3 tri, 4 quad)

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: Operation lamp flashes N times; Timer lamp off for E codes, on for F codes, flashing for P codes.