Carrier AC error codes – VRF Full DC Inverter - indoor units

14 codes from the Carrier service manual, with what each one means and the usual causes. Hi-wall and cassette use some codes differently (E0) - check the indoor type.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

FE

No address at first power-on

What our technician checks
  • X Power IDU: auto addressing (set SW6, power off/on ODU+IDU, wait 6-12 min) or manual. Others: manual addressing by remote after re-powering ODU.
Book a technician for FE

H0

M-Home not matching

Book a technician for H0

E0

Hi-wall: outdoor power supply fault (phase loss/sequence). Cassette: mode conflict

What our technician checks
  • Hi-wall: check ODU supply & phase (see ODU E1). Cassette: match IDU mode to the system (heating has priority).
Book a technician for E0

E1

Indoor-outdoor communication error

What our technician checks
  • Check P-Q-E communication wire for open/short (measure resistance), daisy-chain (hand-in-hand) layout, shielding, distance from power cables, lamps/transformers nearby, wire length. All IDUs powered? Duplicate addresses? Voltage P/Q to E about DC 2.5 V (0 V or 5 V = 485 chip faulty). 485 chip 13089 on IDU board.
Book a technician for E1

E2

Room temperature sensor T1 fault

What our technician checks
  • Sensor plugged in
  • sensor open/short.
Book a technician for E2

E3

Middle evaporator sensor T2 fault

What our technician checks
  • Sensor plugged in
  • sensor open/short.
Book a technician for E3

E4

Evaporator outlet sensor T2B fault

What our technician checks
  • Sensor plugged in
  • sensor open/short.
Book a technician for E4

E5

Hi-wall: T3 / T4 / discharge T7 sensor fault

What our technician checks
  • Check the outdoor sensors.
Book a technician for E5

E6

Hi-wall: mode conflict

What our technician checks
  • Heating has priority in a 2-pipe system
  • cooling IDUs conflict when another is heating.
Book a technician for E6

E7

EEPROM malfunction

What our technician checks
  • EEPROM pins seated
  • EEPROM broken
  • PCB wet/damaged.
Book a technician for E7

EE

Water level alarm

What our technician checks
  • Drain blocked
  • drain lift too high
  • float switch connection & condition.
Book a technician for EE

ED

Outdoor unit malfunction

What our technician checks
  • Read the code on the outdoor unit display.
Book a technician for ED

IDU dead

Indoor board has no power

What our technician checks
  • TRANS IN 220 V
  • transformer output AC 14.5 V (brown), AC 10.5 V (yellow)
  • 7085 regulator DC +5 V / +12 V.
Book a technician for IDU dead

IDU leaking

Indoor unit leaking water

What our technician checks
  • Drain pump, float switch wire, drain slope 1/100, lift height, blocked outlet, insulation at joints, main drain blocked.
Book a technician for IDU leaking

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.