Samsung AC error codes – Inverter split AR09/12/18/24HSF

39 codes from the Samsung service manual, with what each one means and the usual causes. Indoor shows the code on the 7-segment display. Outdoor PBA has 3 LEDs: YEL, GRN, RED (on / off / blinking). Normal outdoor display: RED on, GRN blinking, YEL off.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

E101also E102

Communication error between indoor and outdoor unit

Usual causes

  • Indoor-outdoor connecting cable loose, wrong or cut
  • Power cable and communication cable crossed
  • Indoor or outdoor PBA has no power
  • Indoor PBA or outdoor PBA faulty
What our technician checks
  • Switch off, wait, restart - see if the error returns
  • Check all 5 connecting wires are on matching terminals indoor and outdoor
  • Check power reaches both units (indoor lamp / outdoor LEDs)
Book a technician for E101

E121

Indoor room temperature sensor error

Usual causes

  • Sensor connector loose
  • Sensor open/short (resistance out of range)
  • Indoor PBA faulty
What our technician checks
  • Unplug sensor from PBA and measure: 10 kΩ ±3% at 25°C (20°C 12.09k, 30°C 8.31k, 35°C 6.94k, 40°C 5.83k)
  • Refit sensor, power on and measure voltage at connector pins #1-#2: below 0.5 V or above 4.5 V means PBA problem
Book a technician for E121

E122also E123

Indoor coil sensor error (Eva-MID / Eva-IN pipe sensor)

Usual causes

  • Sensor connector loose or sensor out of its pipe holder
  • Sensor open/short
  • Indoor PBA faulty
What our technician checks
  • Measure sensor pins #3-#4 and #5-#6: 10 kΩ ±3% at 25°C (20°C 12.09k, 30°C 8.31k)
  • Power on: pin voltage below 0.5 V or above 4.5 V = PBA fault
Book a technician for E122

E154

Indoor BLDC fan motor error (speed feedback missing)

Usual causes

  • Fan motor connector CN72 loose
  • Fan motor shorted / seized
  • Indoor PBA fan drive faulty
  • Supply voltage wrong
What our technician checks
  • Power off, unplug CN72, check for short between pins #1-#6 of the motor
  • Power on: CN72 #1-#3 should be over 250 V DC
  • During operation CN72 #3-#5 and #3-#6 should be 1-15 V DC
Book a technician for E154

E162

Indoor EEPROM error

Usual causes

  • Indoor PBA EEPROM corrupted
What our technician checks
  • Power reset
Book a technician for E162

E163

Option code error (indoor option not set / wrong)

Usual causes

  • Wrong option code after PBA change
What our technician checks
  • Check option code matches the model
Book a technician for E163

E203

Communication time-out between inverter micom and main micom (outdoor PBA)

Usual causes

  • Outdoor PBA internal fault
  • Power noise
What our technician checks
  • Power reset
Book a technician for E203

E221

Outdoor (ambient) temperature sensor error

Usual causes

  • Connector CN251 loose or wrong position
  • Sensor open/short
  • Outdoor PBA faulty
What our technician checks
  • Check CN251 fitted correctly (by colour)
  • Measure CN251 #1-#2: 10 kΩ ±3% at 25°C
  • Power on: voltage below 0.5 V or above 4.5 V = PBA fault
Book a technician for E221

E231

Outdoor condenser (coil) temperature sensor error

Usual causes

  • CN251 loose
  • Sensor open/short
  • Outdoor PBA faulty
What our technician checks
  • Measure CN251 #5-#6: 10 kΩ ±3% at 25°C
  • Power on: below 0.5 V or above 4.5 V = PBA fault
Book a technician for E231

E251

Discharge temperature sensor error

Usual causes

  • CN251 loose
  • Sensor open/short
  • Outdoor PBA faulty
What our technician checks
  • Measure CN251 #3-#4: 200 kΩ ±3% at 25°C (20°C 242k, 30°C 166k, 35°C 138k, 40°C 115k)
  • Power on: below 0.5 V or above 4.5 V = PBA fault
Book a technician for E251

E416

Discharge over-temperature (compressor running too hot)

Usual causes

  • Gas shortage / leak
  • Compressor locking
  • Very high outdoor temperature or blocked airflow
  • EEPROM data wrong
  • Outdoor PBA fault
What our technician checks
  • Wait 30 min-1 hr, restart
  • Check gas pressure and leaks
  • Check condenser clean and fan running
Book a technician for E416

E422

EEV or service valve closed (self-diagnosis)

Usual causes

  • Service valve not fully open
  • EEV coil unplugged (CN701) or EEV stuck
  • Gas leak / low charge
  • Indoor Eva-in sensor out of position
What our technician checks
  • Check indoor Eva-in sensor position
  • Restart after 20 min
  • Listen for EEV clicking at power on, check CN701
  • Check refrigerant pressure
Book a technician for E422

E440

Operation stopped - outdoor temperature out of range (heating)

Usual causes

  • Outdoor temperature over 40°C or under -30°C in heat mode
What our technician checks
  • Check temperature around outdoor unit
Book a technician for E440

E441

Operation stopped - outdoor temperature out of range (cooling)

Usual causes

  • Outdoor temperature under -7°C in cool mode
What our technician checks
  • Check temperature around outdoor unit
Book a technician for E441

E458

Outdoor BLDC fan motor error

Usual causes

  • Motor connector CN901 loose
  • Obstruction at the propeller
  • Motor shorted
  • Outdoor PBA fan drive faulty
What our technician checks
  • Check nothing blocks the fan
  • Unplug CN901: short between pins #1-#6 = motor bad
  • CN901 #1-#3 over 250 V DC
  • Running: #3-#5 and #3-#6 between 1-15 V DC
Book a technician for E458

E461

Compressor starting error

Usual causes

  • Compressor wires loose or wrong order
  • Compressor winding / insulation fault
  • EEPROM data wrong
  • Outdoor PBA (IPM) fault
What our technician checks
  • Compressor wire order U-RED, V-BLUE, W-YELLOW
  • Measure U-V, V-W, W-U resistance (should be equal) and insulation to body
Book a technician for E461

E462

AC input current limit trip (PFC over current)

Usual causes

  • Overload - very hot outdoor, dirty coils
  • Temperature sensor out of place giving wrong reading
  • PFC shunt resistor open (R410-R412 / R408-R410)
  • Compressor cable / power terminal loose
What our technician checks
  • Check site load conditions
  • Check sensor positions and values
  • Check compressor and power terminal connections
Book a technician for E462

E464

IPM over current (O.C) error

Usual causes

  • IPM shunt resistor open
  • Abnormal overload condition
  • Sensor detached or wrong reading
  • Compressor winding fault / wires loose
What our technician checks
  • Check compressor wire connections
  • Check site load (indoor/outdoor temperature)
  • Check sensor position and values
  • Check compressor winding resistance and insulation
Book a technician for E464

E465

Compressor voltage / current limit error

Usual causes

  • IPM shunt open
  • Overload
  • Sensor error
  • Compressor winding fault
What our technician checks
  • Same as E464: wiring, load, sensors, compressor resistance/insulation
Book a technician for E465

E466

DC-link voltage under / over

Usual causes

  • Supply voltage outside 180-270 V AC
  • Reactor wire loose
  • DC-link capacitor or sensing resistor fault on outdoor PBA
What our technician checks
  • Input voltage at power cord 180-270 V AC
  • DC-link voltage in operation 280-320 V DC
  • DC-link sensing voltage 0.2-4.0 V DC
  • Reactor insulation
Book a technician for E466

E467

Compressor wire missing / rotation error

Usual causes

  • Compressor lead disconnected or wrong order
  • Compressor winding fault
  • Outdoor PBA fault
What our technician checks
  • Check PBA-to-compressor wiring U-RED, V-BLUE, W-YELLOW
  • Winding resistance and insulation
Book a technician for E467

E468

Current sensor error

Usual causes

  • PFC or IPM shunt resistor open
  • Short/open around current sensing IC (IC451)
What our technician checks
  • Check shunt resistor values
Book a technician for E468

E469

DC-link voltage sensor error

Usual causes

  • Abnormal input voltage
  • Reactor wire loose
  • DC-link capacitor / resistor fault
What our technician checks
  • DC-link voltage in operation 280-320 V DC
  • Sensing voltage 0.2-4.8 V DC
  • Reactor insulation
Book a technician for E469

E470

Outdoor EEPROM data error (no data)

Usual causes

  • EEPROM not downloaded after PBA change
  • Short around micom / EEPROM connector
What our technician checks
  • Was a new PBA fitted without EEPROM data?
Book a technician for E470

E471

EEPROM / OTP data error between main micom and inverter micom

Usual causes

  • EEPROM data mismatch after PBA change
  • Outdoor PBA fault
Book a technician for E471

E472

AC zero-cross signal error

Usual causes

  • Power noise at customer's house
  • Recent power failure
  • Outdoor PBA fault
What our technician checks
  • Check supply quality
Book a technician for E472

E474

Heatsink (IPM) temperature sensor error

Usual causes

  • PBA-heatsink screws loose / gap
  • Outdoor fan not running
  • Control-box cover not fitted
What our technician checks
  • Check the 4 heatsink screws
  • Check outdoor fan running
Book a technician for E474

E483

Over-voltage protection (hardware DC-link)

Usual causes

  • Input voltage too high (above 270 V AC
  • 300 V AC is damaging)
  • Reactor / DC-link circuit fault
What our technician checks
  • Measure supply voltage
  • DC-link 280-320 V DC in operation
Book a technician for E483

E484

PFC over load

Usual causes

  • Low/high supply voltage
  • Reactor wire loose
  • PFC resistor fault
What our technician checks
  • Same as E466
Book a technician for E484

E485

Input current sensor error

Usual causes

  • PFC / IPM shunt open
  • Current sensing circuit fault
What our technician checks
  • Check shunt resistors
Book a technician for E485

E488

AC input voltage sensor error

Usual causes

  • Abnormal input voltage
  • Reactor wire loose
  • PFC resistor (R105-R108) fault
What our technician checks
  • DC-link sensing voltage 0.2-4.8 V DC in operation
  • Reactor insulation
Book a technician for E488

E500

Heatsink over-temperature

Usual causes

  • Heatsink screws loose, poor contact
  • Outdoor fan not running / blocked airflow
  • Very hot site
What our technician checks
  • Check heatsink screws
  • Check outdoor fan and airflow
Book a technician for E500

E554

Gas leak error

Usual causes

  • Low refrigerant / leak
  • Indoor Eva-in sensor out of position
  • EEV not working or unplugged (CN701)
  • Pipe crack
What our technician checks
  • Check Eva-in sensor position
  • Restart after 20 min
  • Check EEV connection and listen for it at power on
  • Check gas pressure, find leak
Book a technician for E554

E556

Capacity mismatch between indoor and outdoor unit

Usual causes

  • Indoor and outdoor units of different capacity
  • Wrong indoor option code
  • Wrong outdoor EEPROM data
What our technician checks
  • Check BTU of both units match
Book a technician for E556

No power (outdoor)

Outdoor unit dead - no LEDs (not displayed)

Usual causes

  • Supply missing
  • L/N/E or communication wire wrongly connected
  • Fuse F001 open
  • SMPS PBA fault
What our technician checks
  • Terminal block L-N 200-240 V AC
  • Fuse F001
  • SMPS outputs: 15 V (14-15), 12 V (11-13), 5 V (4.5-5.5)
  • DC-link capacitor 280-320 V DC after 3 min
Book a technician for No power (outdoor)

Louver not moving

Up/down, left/right or grille louver motor not working (not displayed)

Usual causes

  • Louver motor connector loose (CN61-CN63)
  • Louver motor faulty
  • PBA output faulty
What our technician checks
  • Unplug 30 s and retry swing
  • Check voltage changes on pins #2-#5 of CN61/62/63 when swing pressed
Book a technician for Louver not moving

Remote not working

Indoor unit not receiving remote signal

Usual causes

  • Display PBA connector loose
  • Weak remote batteries
  • Interference from electronic / CFL lights
What our technician checks
  • Check connector and batteries
  • Switch off room lights and test
Book a technician for Remote not working

Indoor dead

Indoor unit has no power / lamp off

Usual causes

  • Fuse open
  • Indoor fan motor short
  • Power circuit / switching transformer fault
  • Terminal block thermal fuse opened (loose indoor-outdoor connection caused heating)
What our technician checks
  • Check 1st and 2nd fuse on indoor PCB
  • Bridge (BD71) input 200-240 V AC
  • 12 V and 5 V on PCB
  • Check terminal block thermal fuse
Book a technician for Indoor dead

Wi-Fi LED

Wi-Fi kit status LED: ON = connected; blink 0.5 s = router OK but no internet; blink 3 s = not connected to router; OFF = kit not connected to AC

Usual causes

  • Internet down
  • Router off / wrong setup
  • Kit not connected to indoor unit
What our technician checks
  • Check router and internet
  • Check kit cable
Book a technician for Wi-Fi LED

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.