Midea AC error codes – Multi-split indoor - Console series
10 codes from the Midea service manual, with what each one means and the usual causes. Read Operation / Timer / Defrost lamps. ✱ fast flash, ◎ slow flash, ● on, ○ off.
You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.
Op✱ T○ D○
T1 room sensor open/short
Usual causes
- Sensor connector loose
- Sensor open or short
- PCB input circuit fault
What our technician checks
- Check sensor-to-PCB connection
- Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Op○ T○ D✱
T2 coil sensor open/short
Usual causes
- Sensor connector loose
- Sensor open or short
- PCB input circuit fault
What our technician checks
- Check sensor-to-PCB connection
- Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Op○ T✱ D○
Indoor / outdoor communication error
Usual causes
- Wrong / loose wiring between indoor and outdoor terminals
- Signal line S fault
- IPM or PFC board not powered (multi outdoor)
- Reactor disconnected
- Wrong number of indoor units detected
- Indoor or outdoor PCB fault
What our technician checks
- Power off at breaker, power on again
- Check wiring follows the wiring diagram
- Measure Vs (voltage between S and L2/N): it should swing between positive and negative
- With all indoors off, check IPM power LED on and PFC LED (qua-zone)
- Outdoor check button: press 18 times to see how many indoor units are detected (2 dual, 3 tri, 4 quad)
Op✱ T✱ D○
Indoor EEPROM malfunction
Usual causes
- EEPROM chip loose (socket type)
- Indoor PCB faulty
What our technician checks
- Switch off 1 minute, switch on
Op✱ T○ D✱
IPM module protection
Usual causes
- IPM P-N voltage wrong (needs 277-356 V DC for 14-27K, 277-410 V DC for 36K)
- Supply not 220-240 V
- Loose cable main board-IPM
- Compressor leads loose / wrong
- Bridge rectifier shorted
- Reactor wire broken (∞ Ω) or PFC module faulty (M5OA-36)
- IPM module, main board or compressor faulty
What our technician checks
- Measure P-N on IPM
- Check supply voltage and wiring
- Check cable main board-IPM and compressor connections
- Measure bridge rectifier: no terminal pair should read 0 Ω
- Measure reactor: open (∞) = broken
- Compressor phase-phase U-V, U-W, V-W 60-150 V AC when running
Op✱ T✱ D✱
T3 or T4 outdoor sensor open/short
Usual causes
- Sensor connector loose
- Sensor open or short
- PCB input circuit fault
What our technician checks
- Check sensor-to-PCB connection
- Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Op✱ T● D○
Compressor top temperature protection
Usual causes
- Compressor not running / wiring loose
- Low refrigerant
- Compressor top overload protector faulty
- Capillary / pipe blockage
- Outdoor main PCB fault
What our technician checks
- Is the compressor running? check connections
- Check refrigerant circulation (pressures)
- Check overload protector continuity
Op✱ T◎ D○
Inverter compressor drive protection
Usual causes
- Same as IPM protection: supply, P-N voltage, IPM, compressor, reactor
What our technician checks
- Follow IPM module protection checks
Op✱ T○ D●
Mode conflict
Usual causes
- Indoor units of the multi system set to conflicting modes (one cooling, one heating)
What our technician checks
- Check modes on all indoor units
Op✱ T● D✱
Indoor fan speed out of control
Usual causes
- Cross-flow fan stuck or bearing worn
- Fan motor wiring loose
- Fan motor winding fault
- Indoor PCB drive fault
What our technician checks
- Power off 1 minute, restart
- Turn the cross-flow fan by hand - should spin freely
- Disconnect fan from motor and check bearing
- Check motor wires and motor resistance
Code not here, or still showing?
Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.
Other code lists
- Samsung AC error codes – Inverter split AR09/12/18/24HSF
- Midea AC error codes – Multi-split indoor - 9V, Vertu, 9A, Corona, R, Y, X series
- Midea AC error codes – Multi-split indoor - NEOLA, PREMIER, OASIS series
- Midea AC error codes – Multi-split indoor - A5 Duct series
- Midea AC error codes – Multi-split indoor - Cassette series
- Midea AC error codes – Multi-split indoor - Ceiling & Floor series