10 codes from the Midea service manual, with what each one means and the usual causes. No digital code - read the lamps: Op = Operation, T = Timer, D = Defrost, A = Alarm. ✱ flash, ● on, ○ off.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

Op✱ T○ D○ A○

T1 room sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for Op✱ T○ D○ A○

Op○ T○ D✱ A○

T2 coil sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for Op○ T○ D✱ A○

Op○ T✱ D○ A○

Indoor / outdoor communication error

Usual causes

  • Wrong / loose wiring between indoor and outdoor terminals
  • Signal line S fault
  • IPM or PFC board not powered (multi outdoor)
  • Reactor disconnected
  • Wrong number of indoor units detected
  • Indoor or outdoor PCB fault
What our technician checks
  • Power off at breaker, power on again
  • Check wiring follows the wiring diagram
  • Measure Vs (voltage between S and L2/N): it should swing between positive and negative
  • With all indoors off, check IPM power LED on and PFC LED (qua-zone)
  • Outdoor check button: press 18 times to see how many indoor units are detected (2 dual, 3 tri, 4 quad)
Book a technician for Op○ T✱ D○ A○

Op○ T○ D○ A✱

Full-water (drain) malfunction

Usual causes

  • Water-level (float) switch not plugged in
  • Float switch broken
  • Drain pump faulty / drain blocked
  • Indoor PCB fault
What our technician checks
  • Check float switch connector
  • Check float switch continuity
  • Check drain pump runs and drain line is clear
Book a technician for Op○ T○ D○ A✱

Op✱ T✱ D○ A○

Indoor EEPROM malfunction

Usual causes

  • EEPROM chip loose (socket type)
  • Indoor PCB faulty
What our technician checks
  • Switch off 1 minute, switch on
Book a technician for Op✱ T✱ D○ A○

Op✱ T○ D○ A●

IPM module protection

Usual causes

  • IPM P-N voltage wrong (needs 277-356 V DC for 14-27K, 277-410 V DC for 36K)
  • Supply not 220-240 V
  • Loose cable main board-IPM
  • Compressor leads loose / wrong
  • Bridge rectifier shorted
  • Reactor wire broken (∞ Ω) or PFC module faulty (M5OA-36)
  • IPM module, main board or compressor faulty
What our technician checks
  • Measure P-N on IPM
  • Check supply voltage and wiring
  • Check cable main board-IPM and compressor connections
  • Measure bridge rectifier: no terminal pair should read 0 Ω
  • Measure reactor: open (∞) = broken
  • Compressor phase-phase U-V, U-W, V-W 60-150 V AC when running
Book a technician for Op✱ T○ D○ A●

Op✱ T● D○ A○

T3 or T4 outdoor sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C
Book a technician for Op✱ T● D○ A○

Op✱ T● D○ A●

Outdoor voltage protection

Usual causes

  • Supply voltage wrong (should be about 220 V AC, unit works 190-264 V)
  • Power board fault
  • Bridge rectifier fault
  • IPM board fault
What our technician checks
  • Measure outdoor L-N: about 220 V AC
  • Measure IPM board P-N: 280-400 V DC
  • Rectifier: input 220-230 V AC gives about 310 V DC
Book a technician for Op✱ T● D○ A●

Op✱ T○ D● A○

Compressor top temperature protection

Usual causes

  • Compressor not running / wiring loose
  • Low refrigerant
  • Compressor top overload protector faulty
  • Capillary / pipe blockage
  • Outdoor main PCB fault
What our technician checks
  • Is the compressor running? check connections
  • Check refrigerant circulation (pressures)
  • Check overload protector continuity
Book a technician for Op✱ T○ D● A○

Op✱ T○ D● A●

Mode conflict

Usual causes

  • Indoor units of the multi system set to conflicting modes (one cooling, one heating)
What our technician checks
  • Check modes on all indoor units
Book a technician for Op✱ T○ D● A●

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.