Maheshwari HVACAC & HVAC experts · Udaipur

Panasonic AC error codes – Room / split AC

37 codes from the Panasonic service manual, with what each one means and the usual causes. Read the code: hold CHECK on the remote 5 s (pin), then press TIMER up/down until the unit beeps - that code is the fault. H00 = no fault stored. Checks are standard practice.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

H11

Indoor-outdoor communication fault

What our technician checks
  • Interconnect cable: correct terminal order (L, N, signal, earth), no loose screw or joint, cable not run with other power cables. Is the outdoor unit powered (LED on outdoor PCB)? Signal line voltage fluctuates when healthy. Check outdoor fuse and reactor.
Book a technician for H11

H12

Indoor capacity mismatch

What our technician checks
  • Indoor and outdoor model numbers are a matching pair? Correct capacity / model setting on the board.
Book a technician for H12

H14

Indoor intake air sensor fault

What our technician checks
  • Room (return air) sensor: unplug and measure - most split ACs use 10 kΩ at 25°C (about 12.6 kΩ at 20°C, 8 kΩ at 30°C). Open or short = faulty. Check connector on the indoor PCB.
Book a technician for H14

H15

Compressor temperature sensor fault

What our technician checks
  • Discharge pipe sensor: measure (typically 50-200 kΩ at 25°C, brand dependent) and check it is fixed on the discharge pipe.
Book a technician for H15

H16

Outdoor current transformer (CT) fault

What our technician checks
  • Current sensing circuit on the outdoor board.
Book a technician for H16

H17

Outdoor suction sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H17

H19

Indoor fan motor locked

What our technician checks
  • Indoor blower turns freely by hand? Blower wheel clean, not rubbing? Fan motor connector, motor supply (AC: capacitor
  • DC: about 310 V DC + 15 V and feedback signal).
Book a technician for H19

H21

Indoor float switch fault

What our technician checks
  • Drain pump runs, float switch free, drain pipe slope and blockage.
Book a technician for H21

H23

Indoor heat exchanger sensor 1 fault

What our technician checks
  • Indoor coil (pipe) sensor: unplug and measure (commonly 10 kΩ or 5 kΩ at 25°C depending on brand). Check it is clipped into the coil sensor pocket.
Book a technician for H23

H24

Indoor heat exchanger sensor 2 fault

What our technician checks
  • Indoor coil (pipe) sensor: unplug and measure (commonly 10 kΩ or 5 kΩ at 25°C depending on brand). Check it is clipped into the coil sensor pocket.
Book a technician for H24

H27

Outdoor air sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H27

H28

Outdoor heat exchanger sensor 1 fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H28

H30

Outdoor discharge pipe sensor fault

What our technician checks
  • Discharge pipe sensor: measure (typically 50-200 kΩ at 25°C, brand dependent) and check it is fixed on the discharge pipe.
Book a technician for H30

H32

Outdoor heat exchanger sensor 2 fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H32

H33

Indoor/outdoor misconnection (wrong voltage / wiring)

What our technician checks
  • Interconnect cable: correct terminal order (L, N, signal, earth), no loose screw or joint, cable not run with other power cables. Is the outdoor unit powered (LED on outdoor PCB)? Signal line voltage fluctuates when healthy. Check outdoor fuse and reactor.
Book a technician for H33

H34

Outdoor heat-sink sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H34

H36

Outdoor gas pipe sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H36

H37

Outdoor liquid pipe sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H37

H38

Indoor/outdoor brand code mismatch

What our technician checks
  • Indoor and outdoor model numbers are a matching pair? Correct capacity / model setting on the board.
Book a technician for H38

H41

Wiring or piping connection fault

What our technician checks
  • Interconnect cable: correct terminal order (L, N, signal, earth), no loose screw or joint, cable not run with other power cables. Is the outdoor unit powered (LED on outdoor PCB)? Signal line voltage fluctuates when healthy. Check outdoor fuse and reactor.
Book a technician for H41

H64

Outdoor high pressure sensor fault

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for H64

H97

Outdoor fan motor locked

What our technician checks
  • Outdoor fan turns freely (bearing)? Leaves / debris? DC fan: motor supply from the outdoor PCB and feedback wire.
Book a technician for H97

H98

Indoor high pressure protection (heating)

What our technician checks
  • Condenser dirty or air recirculating, outdoor fan slow, overcharge, air / nitrogen in system, valves closed (heating: indoor filter / fan).
Book a technician for H98

H99

Indoor freeze protection

What our technician checks
  • Indoor filter / coil dirty, blower slow, low gas, very low set temperature with low indoor load.
Book a technician for H99

F11

4-way valve switching fault

What our technician checks
  • 4-way valve coil voltage and resistance
  • valve sticking (heating models).
Book a technician for F11

F16

Total running current protection

What our technician checks
  • Supply voltage under load, condenser dirty or outdoor fan slow, overcharge, air in system, compressor current against rated.
Book a technician for F16

F17

Indoor standby unit freezing

What our technician checks
  • Indoor filter / coil dirty, blower slow, low gas, very low set temperature with low indoor load.
Book a technician for F17

F87

Control box overheat

What our technician checks
  • Heat-sink fixing and paste, outdoor airflow, high ambient, heat-sink sensor.
Book a technician for F87

F90

PFC circuit protection / compressor control communication

What our technician checks
  • Power off, wait for capacitors to discharge. Compressor U-V, V-W, W-U equal (about 0.5-3 Ω) and >10 MΩ to earth. Diode test the IPM P/N to U/V/W. Check DC bus (about 310 V DC on 230 V supply), heat-sink paste and screws, condenser cleanliness, supply voltage, overcharge.
Book a technician for F90

F91

Refrigerant cycle fault (low gas / blockage)

What our technician checks
  • Suction pressure low? Leak test (flare joints, valves, coils) with soap / nitrogen. Valves fully open?
Book a technician for F91

F93

Compressor abnormal speed

What our technician checks
  • Compressor windings equal and not earthed? U/V/W lead order and connection. Refrigerant pressures equalised before start? Board output to compressor.
Book a technician for F93

F94

Compressor discharge pressure protection

What our technician checks
  • Condenser dirty or air recirculating, outdoor fan slow, overcharge, air / nitrogen in system, valves closed (heating: indoor filter / fan).
Book a technician for F94

F95

Outdoor cooling high pressure protection

What our technician checks
  • Condenser dirty or air recirculating, outdoor fan slow, overcharge, air / nitrogen in system, valves closed (heating: indoor filter / fan).
Book a technician for F95

F96

Power transistor (IPM) overheating

What our technician checks
  • Heat-sink fixing and paste, outdoor airflow, high ambient, heat-sink sensor.
Book a technician for F96

F97

Compressor overheating

What our technician checks
  • Low refrigerant charge (most common), blocked expansion valve / capillary, EEV not opening, discharge sensor reading wrong.
Book a technician for F97

F98

Total running current protection

What our technician checks
  • Supply voltage under load, condenser dirty or outdoor fan slow, overcharge, air in system, compressor current against rated.
Book a technician for F98

F99

Outdoor DC peak detected

What our technician checks
  • Power off, wait for capacitors to discharge. Compressor U-V, V-W, W-U equal (about 0.5-3 Ω) and >10 MΩ to earth. Diode test the IPM P/N to U/V/W. Check DC bus (about 310 V DC on 230 V supply), heat-sink paste and screws, condenser cleanliness, supply voltage, overcharge.
Book a technician for F99

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.