LG AC error codes – Single / multi-split inverter AC

30 codes from the LG service manual, with what each one means and the usual causes. Shown as CHxx on the display; models without a display blink LEDs (pattern varies by model - see its manual). Checks are standard practice.

You can safely switch the unit off at the switch, wait 5 minutes and switch on again. Don't open the unit, touch wiring or handle gas: these checks need a trained technician.

1also CH01

Indoor room (return air) sensor open/short

What our technician checks
  • Room (return air) sensor: unplug and measure - most split ACs use 10 kΩ at 25°C (about 12.6 kΩ at 20°C, 8 kΩ at 30°C). Open or short = faulty. Check connector on the indoor PCB.
Book a technician for 1

2also CH02

Indoor inlet pipe sensor open/short

What our technician checks
  • Indoor coil (pipe) sensor: unplug and measure (commonly 10 kΩ or 5 kΩ at 25°C depending on brand). Check it is clipped into the coil sensor pocket.
Book a technician for 2

5also CH05

Indoor-outdoor communication failure

What our technician checks
  • Interconnect cable: correct terminal order (L, N, signal, earth), no loose screw or joint, cable not run with other power cables. Is the outdoor unit powered (LED on outdoor PCB)? Signal line voltage fluctuates when healthy. Check outdoor fuse and reactor.
Book a technician for 5

6also CH06

Indoor outlet pipe sensor open/short

What our technician checks
  • Indoor coil (pipe) sensor: unplug and measure (commonly 10 kΩ or 5 kΩ at 25°C depending on brand). Check it is clipped into the coil sensor pocket.
Book a technician for 6

9also CH09

Indoor EEPROM error

What our technician checks
  • Power off 3 min and restart.
Book a technician for 9

10also CH10

Indoor fan locked (motor failure)

What our technician checks
  • Indoor blower turns freely by hand? Blower wheel clean, not rubbing? Fan motor connector, motor supply (AC: capacitor
  • DC: about 310 V DC + 15 V and feedback signal).
Book a technician for 10

12also CH12

Indoor middle pipe sensor open/short

What our technician checks
  • Indoor coil (pipe) sensor: unplug and measure (commonly 10 kΩ or 5 kΩ at 25°C depending on brand). Check it is clipped into the coil sensor pocket.
Book a technician for 12

21also CH21

DC peak / IPM fault

What our technician checks
  • Power off, wait for capacitors to discharge. Compressor U-V, V-W, W-U equal (about 0.5-3 Ω) and >10 MΩ to earth. Diode test the IPM P/N to U/V/W. Check DC bus (about 310 V DC on 230 V supply), heat-sink paste and screws, condenser cleanliness, supply voltage, overcharge.
Book a technician for 21

22also CH22

CT2 - AC input current too high

What our technician checks
  • Supply voltage under load, condenser dirty or outdoor fan slow, overcharge, air in system, compressor current against rated.
Book a technician for 22

23also CH23

DC link voltage too low

What our technician checks
  • Measure mains under load (single phase normally 200-250 V). Loose neutral, undersized cable, stabiliser.
Book a technician for 23

25also CH25

Supply voltage too low or too high

What our technician checks
  • Measure mains under load (single phase normally 200-250 V). Loose neutral, undersized cable, stabiliser.
Book a technician for 25

26also CH26

Inverter compressor locked / not rotating

What our technician checks
  • Compressor windings equal and not earthed? U/V/W lead order and connection. Refrigerant pressures equalised before start? Board output to compressor.
Book a technician for 26

27also CH27

PSC / PFC fault (AC-DC converter current high)

What our technician checks
  • Power off, wait for capacitors to discharge. Compressor U-V, V-W, W-U equal (about 0.5-3 Ω) and >10 MΩ to earth. Diode test the IPM P/N to U/V/W. Check DC bus (about 310 V DC on 230 V supply), heat-sink paste and screws, condenser cleanliness, supply voltage, overcharge.
Book a technician for 27

28also CH28

Inverter DC voltage too high

What our technician checks
  • Measure mains under load (single phase normally 200-250 V). Loose neutral, undersized cable, stabiliser.
Book a technician for 28

29also CH29

Inverter compressor current too high

What our technician checks
  • Power off, wait for capacitors to discharge. Compressor U-V, V-W, W-U equal (about 0.5-3 Ω) and >10 MΩ to earth. Diode test the IPM P/N to U/V/W. Check DC bus (about 310 V DC on 230 V supply), heat-sink paste and screws, condenser cleanliness, supply voltage, overcharge.
Book a technician for 29

31also CH31

CT sensor reading too low

What our technician checks
  • Current sensing circuit on the outdoor board.
Book a technician for 31

32also CH32

Discharge pipe temperature too high

What our technician checks
  • Low refrigerant charge (most common), blocked expansion valve / capillary, EEV not opening, discharge sensor reading wrong.
Book a technician for 32

40also CH40

CT sensor open/short

What our technician checks
  • Current sensing circuit on the outdoor board.
Book a technician for 40

41also CH41

Discharge pipe sensor open/short

What our technician checks
  • Discharge pipe sensor: measure (typically 50-200 kΩ at 25°C, brand dependent) and check it is fixed on the discharge pipe.
Book a technician for 41

44also CH44

Outdoor air sensor open/short

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for 44

45also CH45

Condenser middle sensor open/short

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for 45

46also CH46

Suction line sensor open/short

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for 46

48also CH48

Condenser outlet (liquid) sensor open/short

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for 48

53also CH53

Outdoor-indoor communication failure

What our technician checks
  • Interconnect cable: correct terminal order (L, N, signal, earth), no loose screw or joint, cable not run with other power cables. Is the outdoor unit powered (LED on outdoor PCB)? Signal line voltage fluctuates when healthy. Check outdoor fuse and reactor.
Book a technician for 53

60also CH60

Outdoor PCB EEPROM error

What our technician checks
  • Power off 3 min and restart.
Book a technician for 60

61also CH61

Condenser coil temperature too high

What our technician checks
  • Condenser dirty or air recirculating, outdoor fan slow, overcharge, air / nitrogen in system, valves closed (heating: indoor filter / fan).
Book a technician for 61

62also CH62

Inverter heat-sink temperature too high

What our technician checks
  • Heat-sink fixing and paste, outdoor airflow, high ambient, heat-sink sensor.
Book a technician for 62

63also CH63

Condenser coil temperature too low

What our technician checks
  • Suction pressure low? Leak test (flare joints, valves, coils) with soap / nitrogen. Valves fully open?
Book a technician for 63

65also CH65

Heat-sink sensor open/short

What our technician checks
  • Outdoor sensor (ambient / coil / suction): unplug and measure against the brand chart (outdoor ones are usually 10 kΩ, discharge sensors 50-200 kΩ at 25°C).
Book a technician for 65

67also CH67

Outdoor BLDC fan motor locked

What our technician checks
  • Outdoor fan turns freely (bearing)? Leaves / debris? DC fan: motor supply from the outdoor PCB and feedback wire.
Book a technician for 67

Code not here, or still showing?

Send a photo of the display and the model sticker on WhatsApp. We'll tell you what it means and whether it needs a visit.