LG AC low cooling

What it means

Poor cooling - refrigerant cycle check

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If Low cooling comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Air temp difference in/out should be over 8°C. ~0°C diff + low current = all gas leaked. ~8°C + current <80% = leak/clog/compressor. <8°C + current over rated = overcharge. Normal suction 8.5-9.5 kg/cm²G (cooling).

From the LG service manual. These checks use meters and live power – for trained technicians only.

About this series: Only one blink code on this series; the rest are symptom checks from the manual.