LG AC comp/fan not running

What it means

Compressor and outdoor fan do not run

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If Comp/fan not running comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Set cool 1°C below room temp
  • not in fan mode. Room sensor ~10 kΩ at 25°C and placed correctly. RY-COMP: Micom pin 59 = DC 5 V when ON
  • IC01M pin 15 below 1 V when ON, ~12 V when OFF. AC 220/240 V at compressor terminal = PCB OK.

From the LG service manual. These checks use meters and live power – for trained technicians only.

About this series: Only one blink code on this series; the rest are symptom checks from the manual.