Maheshwari HVAC Solutions

Midea AC op✱ t○ d○ a○

What it means

T1 room sensor open/short

Usual causes

  • Sensor connector loose
  • Sensor open or short
  • PCB input circuit fault

What you can safely try

  1. Switch the AC off at the switch or MCB.
  2. Wait 5 minutes, then switch on and start it with the remote.
  3. If Op✱ T○ D○ A○ comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
  • Check sensor-to-PCB connection
  • Measure sensor resistance against table. Sensor table (Appendix 1, T1/T2/T2B/T3/T4): 10 kΩ at 25°C, 12.64k at 20°C, 7.97k at 30°C, 5.18k at 40°C, 35.2k at 0°C

From the Midea service manual. These checks use meters and live power – for trained technicians only.

About this series: No digital code - read the lamps: Op = Operation, T = Timer, D = Defrost, A = Alarm. ✱ flash, ● on, ○ off.