Daikin AC error codes – Split / room AC
Daikin AC C9 error code
What it means
Indoor suction (room) air sensor fault
What you can safely try
- Switch the AC off at the switch or MCB.
- Wait 5 minutes, then switch on and start it with the remote.
- If C9 comes back, note it and call us. Please don’t open the panels, touch wiring or handle gas.
What our technician checks
- Room (return air) sensor: unplug and measure - most split ACs use 10 kΩ at 25°C (about 12.6 kΩ at 20°C, 8 kΩ at 30°C). Open or short = faulty. Check connector on the indoor PCB.
From the Daikin service manual. These checks use meters and live power – for trained technicians only.
About this series: Read the code: hold CANCEL on the remote about 5 s until 00 blinks, press CANCEL repeatedly until a long beep - the code shown then is the fault. Checks are standard Daikin service practice.